OverviewThe HOBO State/Pulse/Event/Runtime data logger records state changes, electronic pulses and mechanical or electrical contact closures from external sensing devices. This logger is ideal for monitoring energy consumption, mechanical equipment operation, and water and gas flow. The HOBO UX90-001 State Logger is available in a standard 128 KB memory model (UX90-001) capable of 84,650 measurements and an expanded 512KB memory version (UX90-001M) capable of over 346,795 measurements.
Highlighted Features
- One logger with 4 recording modes
- Internal reed switch can be used to determine when a door or window is open or closed
- Compatible with a wide range of external sensors
- Ships with 2.5 mm input cable
- Compatible with HOBOware and HOBOware Pro software for logger setup, graphing and analysis
In what environment does this data logger operate?
This data logger operates in an indoor environment.
What measurements does this data logger support?
The UX90-001M data logger supports the following measurements: Event, Kilowatt Hours (kWh), Motor On/Off, Pulse Input, Runtime, State Open/Closed and Water Flow
Preferred Switch State: No magnet present (normally open)
Range: 0 to 3 V DC (USB powered), 0 to 2.5 V DC (battery powered)
Maximum Pulse Frequency: 50 Hz
Maximum State, Event, Runtime Frequency: 1 Hz
Pulse, Event Lockout Time: 0 to 1 second in 100 ms steps
Solid State Switch Closure: Input Low: < 10 K„¦; Input High: > 500 K„¦
Internal Weak Pull-Up: 100 K„¦
Input Impedance: Solid state switch closure: 100 K„¦ pull up
Logging Rate: 1 second to 18 hours, 12 minutes, 15 seconds
Time Accuracy: ±1 minute per month at 25°C (77°F) (see Plot A)
Battery Life: 1 year, typical with logging intervals greater than 1 minute and normally open contacts
Memory:
UX90-001: 128 KB (84,650 measurements, maximum)
UX90-001M: 512 KB (346,795 measurements, maximum)
Download Type: USB 2.0 interface
Download Time: 10 seconds for 128 KB; 30 seconds for 512 KB
Logger Operating Range:
Logging: -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing)
Launch/Readout: 0° to 50°C (32° to 122°F) per USB specification
LCD: LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range
Size: 3.66 x 5.94 x 1.52 cm (1.44 x 2.34 x 0.6 in.)
Weight: 23 g (0.81 oz)
Environmental Rating: IP50